Stampario

Austin backflow Test and Maintenance Report (TMR)

Updated November 1, 2026 · Stampario team

In Austin, every backflow assembly protecting against a health hazard is tested on installation and at least once a year. The tester must hold a TCEQ license and be registered with Austin Water, and must submit a Test and Maintenance Report (TMR) for each assembly within 5 calendar days of the test. Paper is no longer accepted: reports go in online. Austin Water says it will retire its WEIRS system on November 16 and move test submissions to a new application, Klir, going live November 17.

Deadlines

  • Test on installation and at least once a year after that, for assemblies installed to protect against a health hazard
  • TMR submitted within 5 calendar days of each test, one report per assembly
  • Since July 25, 2022 TMRs are accepted only online; paper copies are not
  • Austin Water’s pages do not state a deadline for repairs or retests after a failed test. Check your notice or ask the Cross Connection Control office

What a TMR must include

  • Physical address and location of the assembly, and the cause requiring backflow protection
  • Assembly manufacturer, size, model number and serial number
  • Operational test results, plus a description of repairs and the retest results after repairs
  • Name of the owner or occupant responsible, the owner’s representative and the owner’s complete mailing address
  • Tester’s printed name, signature and license number
  • Test gauge serial number and the date of the operational test

Who can test

Testers must be licensed by the Texas Commission on Environmental Quality (TCEQ): a 40-hour TCEQ-accredited course, the license exam and the fee. They then register with Austin Water with a Water Protection Technician Registration Application and, unless they use their employer’s registered gauges, a Backflow Gauge Registration Form. Tests follow TCEQ-approved methods from the USC Cross Connection Manual, with gauges calibrated by an approved gauge testing company. Austin Water states that three notices of violation within two years lead to suspension of the City registration for one year.

The WEIRS to Klir change

Austin Water’s pages say that on Monday, November 16 it retires WEIRS and moves all Water Protection test submissions to Klir, which is set to go live on Tuesday, November 17. Submissions pending in WEIRS should be finished before 5 pm on Friday, November 13. Registered testers are promised emails about registration and training. Until the pages are updated, the Klir login and steps are not public, so watch your email and the Austin Water tester page.

Rules cited

Austin Water cites Chapter 15-1 (Cross Connection Regulations), which replaced ordinance 040108-3 under ordinance 20250410-002, effective April 21, 2025.

How Stampario fills it

Example Backflow Prevention Assembly Test and Maintenance Report made in Stampario
Backflow test (Texas TCEQ-20700 layout)Example PDF
  • The Texas layout of the backflow report holds the TMR values: assembly make, model, size and serial number, location, readings, repairs, the retest, gauge serial number, and the tester’s license number and signature.
  • The date of the test is on every report, so the 5-day window is easy to check before you key it into the City’s system.
  • Customers get a signed copy right away. You type the same values into the City’s system.

Common questions

Does Austin accept the TCEQ-20700 form?

Austin Water asks for its own Test and Maintenance Report, submitted online. The TCEQ layout carries the same kind of values and is your signed record, but file through the City’s system.

What changes on November 16?

According to Austin Water, WEIRS is retired and test submissions move to Klir, live from November 17. Finish pending WEIRS submissions by 5 pm on November 13.

Sources

Codes change by edition and the authority having jurisdiction (your fire marshal, water purveyor or state agency) decides which rules apply. This page is general information, not legal advice.